Guide to Single Phase Baldor Motor Wiring with Connection Diagrams

Start by identifying the capacitor’s leads on your unit–these are typically marked with C (common) and HR (high-run) or AUX (auxiliary). The main winding connects to the T1 and T2 terminals, while the start winding joins T3 and T4. If the motor lacks explicit terminal labels, use a 120V continuity tester: the pair with lower resistance belongs to the run winding, while the higher-resistance pair is the start winding.
Dual-voltage models (115V/230V) require reconfiguring the bridge between T5 and T6. For 115V operation, link L1 to T1 and T3, then L2 to T2 and T4, leaving T5-T6 open. For 230V, connect L1 to T1, L2 to T2, and bridge T3-T4 to T5-T6. Verify capacitor microfarad ratings–common values for 1 HP units range between 120-200 µF; exceeding these risks winding burnout.
Polarity reversal is critical: swapping L1 and L2 at the run winding terminals (T1/T2) flips rotation. If the shaft spins counterclockwise when viewed from the rear, invert the leads. Use 14 AWG THHN wire for current loads up to 15A; larger motors may need 12 AWG. Always ground the frame to a dedicated earth terminal–absent this, bond to a clean metal surface using a star washer to prevent corrosion gaps.
Before energizing, check voltage drop across the capacitor: a multimeter should read near-zero AC resistance. If the reading climbs above 0.5 ohms, replace the capacitor–failing units cause excessive current draw, tripping breakers or overheating windings. For centrifugal switch failures, manually test spin: if the shaft doesn’t accelerate smoothly within 1-2 seconds, the switch contacts may be welded shut–disassemble the end bell to inspect.
Thermal overload protection default trip points vary: Baldor M3511 units trip at 140°C; adjust via the bimetallic strip’s calibration screw if nuisance trips occur. For frequent start/stop cycles, downgrade to a manual-reset protector–automatic reset models can mask intermittent faults by repeatedly attempting to restart.
Connecting a Capacitor-Start Induction Unit from ABB: Key Schematics and Steps

Locate the terminal box on the unit’s housing–typically a stamped metal lid secured by two screws. Open it to expose six posts labeled U1, U2, Z1, Z2, C1, and C2. U1 and U2 correspond to the main coil leads, while Z1 and Z2 connect to the auxiliary winding. C1 and C2 are reserved for the external capacitor.
Identify the capacitor rating stamped on its case; common values range from 250 µF for 1 HP units to 450 µF for 3 HP variants. Use only non-polarized electrolytic types rated at 250 VAC or higher. Wire color codes may vary: red for run leads, black for start leads, and blue for capacitor terminals. Verify against the nameplate–deviations indicate custom builds.
Attach the capacitor between Z1 and C1. Twist the leads firmly, then secure with crimp connectors or solder to prevent vibration-induced disconnections. Torque terminal screws to 8–12 inch-pounds; overtightening risks thread stripping in the phenolic terminal block.
| Terminal | Function | Typical Wire Gauge |
|---|---|---|
| U1, U2 | Primary winding | 14 AWG |
| Z1, Z2 | Auxiliary winding | 16 AWG |
| C1, C2 | Capacitor leads | 18 AWG |
Power connections require a dedicated 20 A breaker for 1.5 HP models. Route 120 VAC to U1 and the neutral to U2. For 230 VAC configurations, both U1 and U2 receive hot leads–verify jumpers are removed if present from the factory. Miswiring risks coil burnout within 15–30 seconds of startup.
Test rotation by momentarily energizing the circuit. If rotation opposes the required direction, swap either Z1 and Z2 or reverse the capacitor leads–never invert U1 and U2, as this reduces torque by 40%. For dual-voltage units, adjust jumper blocks per the nameplate diagram: a white jumper connects U2 and Z2 for 120 V, while separate leads feed 230 V.
Ground the frame via the green bonding screw in the terminal box. Use 10 AWG copper wire for runs exceeding 25 feet to comply with NEC Article 250. For enclosed installations, mount a centrifugal switch override kit to prevent heat buildup; ABB part #82731 fits 1–2 HP models.
Seal the terminal box with a silicone gasket to block moisture ingress. Apply dielectric grease to terminals before reassembly, focusing on Z1 and Z2 connections–these oxidize faster under start-cycle arcing. Recheck all fasteners after 8 hours of operation; thermal cycling loosens terminals in aluminum housings.
Troubleshooting Voltage Drop During Startup
If lights dim or the unit hesitates at startup, measure voltage across U1-U2 with a true RMS meter. A drop below 90% of rated voltage indicates undersized supply wiring. Upgrade to 12 AWG for 50-foot runs or install a hard-start capacitor–ABB #82723 boosts torque 30% for 1 HP units. For persistent issues, inspect the centrifugal switch; pitted contacts reduce auxiliary winding engagement.
Common Nameplate Anomalies and Their Resolutions
“Code L” on the label denotes a locked-rotor current limit of 15 A for 1 HP units. Exceeding this trips breakers–use a delayed action type (Class CC) if nuisance trips occur. “Service Factor 1.15” permits 15% overload for 30-minute intervals; monitor winding temperature with an infrared thermometer–readings above 85°C degrade insulation. “Thermal Class B” units tolerate 130°C, but extended operation above 110°C voids warranties.
Locating and Matching Leads on a Baldor Capacitor-Start Induction Unit
Begin by removing the terminal cover–typically secured with two screws–to expose the internal connections. Most Baldor capacitor-start models use a standard color-coding system: red (T1) and black (T2) for the main power input, brown and brown/white stripe for the auxiliary winding, and yellow or orange as the common lead for the centrifugal switch or capacitor. Verify these against the nameplate; some older units may deviate, using purple instead of yellow for the common.
Check for embossed markings on the terminal block–look for T1, T2, AUX, and COM or C. If absent, trace the leads back to their origin: the capacitor connects to the auxiliary winding (usually brown) and the common (yellow), while the main winding terminates at T1 and T2. Use a multimeter in continuity mode to confirm–auxiliary windings show higher resistance (often 5–20 ohms) than the main winding (1–5 ohms).
Common mistakes include misidentifying the common lead or reversing T1/T2, leading to reversed rotation or failure to start. If the unit spins backward, swap T1 and T2–no other changes are needed. For dual-voltage configurations (e.g., 115V/230V), locate the jumper beneath the terminal cover; connect T1 to one power lead and T2 to the remaining hot wire for 115V operation, or link T1 and T2 with a jumper for 230V. Always disconnect power before adjusting.
Troubleshooting Unlabeled Terminals
- If colors don’t match standard schemes, measure resistance between pairs:
- Lowest reading = main winding (T1–T2).
- Medium reading = auxiliary winding (brown–common).
- Highest reading = continuity across capacitor (should show transient charge).
- Tag all leads with masking tape before disconnecting to avoid confusion.
- Consult the model-specific manual–Baldor’s 3-digit suffix (e.g.,
L3510) often denotes wiring variations.
After confirming connections, reassemble the terminal cover securely to prevent dust ingress or accidental shorts. For capacitor-start/capacitor-run units, an additional run capacitor (round, metal-cased) may be present–its leads attach between the auxiliary winding and the common. If the unit hums but doesn’t start, the issue is likely a faulty capacitor or centrifugal switch; replace the capacitor first (match microfarad rating ±10%).
Installation Guide: Connecting Start and Run Capacitors in a 1HP AC Drive
Shut off power at the breaker before handling terminals. Use a multimeter set to 1000V AC to confirm zero voltage across L1/L2. Identify the run capacitor–typically oval, 4–20 microfarads–and the start capacitor, round, 70–300 microfarads–for motors between ½ and 2 horsepower. Locate the auxiliary winding leads (often T5 and T8) and the main winding leads (T1 and T4). Double-check against the nameplate: a misconnect risks coil burnout within seconds.
Attach the run capacitor between the auxiliary winding (T5) and the main winding common (T1). Secure with crimp connectors; solder joints corrode under vibration. Route the start capacitor from the auxiliary winding (T8) to the centrifugal switch or potential relay–verify relay coil voltage matches line voltage (120V or 240V) to prevent chatter. If using a relay, ensure coil polarity aligns with L1/L2 orientation; reversing causes arcing. For motors lacking a relay, wire the start capacitor directly to the auxiliary winding but prepare for manual disengagement after spin-up.
Mount capacitors with ½-inch standoffs from the housing–proximity to windings promotes premature dielectric failure. Ground both capacitor cases to the frame with 14 AWG green wire, torque to 12 in-lbs. Test spin direction with a single-cycle start: a hum followed by immediate shutdown suggests reversed T5/T8 polarity. Reverse T5 and re-test; persistent hum indicates relay failure or capacitor degradation–replace components rated for 250VAC minimum, ignoring 125V markings.
After confirmation, apply full load and monitor winding temperatures with a non-contact thermometer. Target is 45°C rise; temperatures exceeding 60°C degrade lubricant and shorten capacitor lifespan. Re-check connections after 24 hours; vibration loosens terminals even when torqued. Keep spare capacitors onsite–start types fail 4x more frequently than run capacitors, often without warning.